KBP-01 UPS set

General information

  • Providing guaranteed power supply for communications equipment with DC 48 V voltage in the cases of temporary absence of mains 220 VAC voltage.

  • For interruptions of mains power supply it provides power supply for the equipment for 24 hours with battery capacity of 40 A/h and load current of up to 0,7 A.

  • For low loads and for short mains 220 VAC interruption periods option with 7,2 A/h batteries is available.

  • Range of input AC voltage is from 150 to 265 V.

  • Maximum load current is 1,2 A.

  • Possibility of installation of additional module for conversion of input 48 VDC into output 250 VDC for power supply for remote equipment with load current up to 160 mA.

  • Protection from short circuits and critical discharge voltage of batteries.

  • Support of network monitoring system.

  • Installation into 19” “euro” cabinet, into AB-02 cabinet (with CSB GP12400 batteries) or direct fixing to the wall (in this case CSB GP1272 batteries are installed into AB-01 cabinet).

Composition of the set

AB-02 cabinet

Floor-mounted cabinet for installation of CSB GP12400 batteries and BP-01 unit (790 * 570 * 300 mm).

AB-01 cabinet

Universal cabinet for installation of CSB GP1272 batteries (440 * 265 * 129 mm).

BP-01

Uninterrupted power supply

CSB GP12400 batteries

12 V; 40 A/h (4 pcs)

CSB GP1272 batteries

12 V; 7,2 A/h (4 pcs)

[Open/Save exploitation manual]

[Open/Save operator’s manual]

BP-01 unit

AB-01 cabinet with batteries

Installation into AB-02 cabinet


ââåðõ