KBP-03 UPS set
General information
Providing guaranteed power supply for communications equipment with DC 48 V voltage in the cases of temporary absence of mains 220 VAC voltage/
For interruptions of mains power supply it provides power supply for the equipment for 24 hours with load current of up to 0,7 A.
Range if input AC voltage is from 150 to 290 V.
Maximum load current 5 A including battery charging current.
Correction power factor of consumption from AC mains.
Protection from short circuits and critical discharge voltage of batteries.
Support of local monitoring via RS-232 interface.
Support of network monitoring system via RS-485 interface.
Installation into 19” “euro” cabinet of floor mounted AB-02 cabinet.
Functionalities
Measuring of mains 220 VAC.
Measuring of battery charge/discharge current.
Measuring of load current.
Disconnecting the load when the current exceeds 5 A and it’s re-connection after lowering the current.
Measuring of battery viltage.
Disconnecting the load when battery voltage drops below 44 V.
Re-connecting the load when the battery voltage rises up above 52 V or when mains 220 VAC re-appears.
Measuring of rotation speed of built-in cooling fans.
Measuring of built-in solid-state elements’ heat-sinks temperature, lowering charge current at limit temperature value.
Indication of mains 220 VAC voltage presence.
Indication of output 48 VDC voltage presence.
Indication of charge current presence (green LED) and discharge current presence (red LED).
Composition of the set
| |
AB-02 cabinet |
Floor mounted cabinet for placing CSB GP12400 batteries and BP-01 unit (790*570*300 mm)
|
BP-03 unit |
UPS
|
CSB GP12400 batteries |
12 V; 40 A/h (4 pcs.)
|
|
[Open/Save exploitation manual]
KBP-03 UPS set |
AB-02 cabinet |
|
|
|